Welcome Customer !

Membership

Help

Shenzhen Simpson Refrigeration Technology Co., Ltd
Custom manufacturer

Main Products:

plast-mach>Products

Shenzhen Simpson Refrigeration Technology Co., Ltd

  • E-mail

    Simpsan@163.com

  • Phone

    189-2749-0225

  • Address

    Simpson Industrial Park, Maoyuan Industrial Zone, Huanguan South Road, Longhua District, Shenzhen

Contact Now

Full liquid screw water source heat pump unit (single unit)

NegotiableUpdate on 04/01
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin
Overview
Full liquid screw water source heat pump unit (single unit)
Product Details
Parameter Table of Full Liquid Screw Water Source Heat Pump Unit Technical Parameters
Model No. of Simpson SPF-380WH SPF-410WH SPF-500WH SPF-520WH SPF-625WH SPF-650WH SPF-750WH SPF-810WH SPF-890WH SPF-1000WH
Use power supply 3Φ-50Hz-380V
Rated Cooling Capacity KW 378 407.9 495.3 517.7 620.1 643.9 749.8 807.1 888.1 991.1
Kcal/h 325080 350800 426000 445300 533300 553800 644800 694100 763800 852400
Operating current of the unit A 132.6 146.4 169.3 182.5 214.4 219 252.8 282.4 300.3 333
Chilled water flow m³/h 65 71 86 90 107 111 129 139 153 171
Cooling water flow m³/h 79 86 103 107 129 133 155 168 184 205
compressor
Compressor
Type of form - Semi sealed screw type<
Quantity Qty PCS 1
Starting mode - Y-Δ
Capacity control % 25%~100% with or without segment control 25%~100% step or less control
Power Supply KW 77.3 86.5 100 107.2 125.4 129.4 150.6 168.7 179.1 198.4
refrigerant
Refrigerant
Type Model - R22
Capacity Capacity Kg 100 100 110 110 140 140 150 150 165 200
evaporator
Evaporator
Type of form - Flooded high efficient shell&tube heat exchanger
Pipe diameter mm 100 100 125 125 125 125 150 150 150 150
condenser
Condenser
Type of form - Horizontal Shell&Tube Type
Pipe diameter mm 100 125 125 125 150 150 150 150 150 200
Safety Device High bottom pressure switch, antifreeze protection, thrombolytic/safety valve, overload protection device, coil overheat protector, temperature automatic protection switch, etc
High & low pressure protection, Anti-freezing protection, Safety valve, Overload protection,coil overheating protection, Temperature automatic protection switch etc.
External dimensions
Dimension
Long (L) mm 3010 3010 3010 3010 3510 3510 3510 3510 3510 3510
Width (W) mm 1260 1260 1260 1260 1350 1350 1400 1400 1400 1400
High (H) mm 1800 1800 1800 1800 1950 1950 2000 2000 2000 2050
Weight Kg 2550 2800 3100 3100 3500 3800 3850 4100 4300 4700
Re: 1. Measurement conditions for the above specification parameters: chilled water inlet temperature of 12 ° C, outlet temperature of 7 ° C, cooling water inlet temperature of 30 ° C, outlet temperature of 35 ° C, fouling coefficient of 0.0001mm ² ° C \ \ W;
Cooling conditions for above specifications: Chilled water inlet 12°C, outlet 7°C, cooling water inle30°C, outlet 35°C, fouling factor 0.0001mm²°C\\W;
2. The above specifications may change due to product improvements without prior notice. If there are special requirements, please specify them before placing an order
The above specification will change without prior notice due to product improvement. Please contact us before order if you have special requirements.