WEG relay RW17-1D3-U017Technical Specifications
overload relay
Reference model: RW17
Number of poles: 3 poles
Installation type: direct installation
Contactor models: CWC07-16, CW07
Installation configuration: 1D
Rated insulation voltage Ui: 690 V
Rated insulation voltage Ui (according to UL): 600 V
Rated impulse withstand voltage Uimp: 6 kV
Rated operating frequency: 25... 400Hz
Suitable for DC loads: Yes
High operating frequency: 15 times/hour
Protection level of main wiring: IP10
Protection level of auxiliary wiring: IP20
Current range: 11-17 A
Large fuse (type 2 coordinated): 40gL/gG
Fuse short-circuit protection (gL/gG): 6gL/gG
Height: 72 mm/2.83 inches
Width: 45 mm/1.77 inches
Depth: 82 mm/3.23 inches
Gross weight: 0.165 kg/0.36 lb
Introduction to WEG Relay RW Series
RW overload relay can protect the load from overheating caused by overload or phase loss. When overload or phase loss occurs in the circuit, the motor current increases. At this point, the increase in current will activate the trip mechanism, thereby driving the auxiliary 95-96 (normally closed) and 97-98 (normally open) actions. Assist in disconnecting the load through the contactor. The disconnection time is related to the overload current and the current set on the relay, which is appropriately represented on the relay trip curve. After tripping, it is necessary to wait for the system to recover in order to reset, which can be done automatically or manually.
Key Features
Provide three pole and two pole versions
Trip thermal class 10
Can be directly connected to compact contactor series from 7 to 32A (CW07, CWC07... 025) and 9... 140 A (CWM9... 105 and CWB 9... 125) contactors without additional accessories
The attachment can be installed on a DIN 35mm (EN 50022) rail or fixed with screws
Develop in accordance with the following standards: IEC 60947-4-1, IEC 60529, IEC 60068, VDE 0106, UL-508
Main homologues: UL, CE, IRAM, BV, NOM ANCE, RCC, PCT
If you need to consult WEG relays and other related information, please feel free to call Ruikuo Automation, and we will do our best to solve your problem.
RiiKOO mainly provides testing, analysis, and application solutions and related equipment for the automotive manufacturing industry. Our main focus is to collaborate with innovators in the industry, providing technology driven products and services to help the automotive manufacturing industry collaborate and apply products more efficiently, efficiently, and conveniently, in order to provide a high-quality user experience.