The significance of monitoring motor speed and forward/reverse rotation:
Motor speed is one of the important parameters for machine startup, shutdown, and stable operation. A sudden change in motor speed may indicate a malfunction in the machine or industrial process. It is important to identify the relationship between vibration and speed in the analysis of motor operation status. When designing centrifugal machines, their speed operating range should avoid the machine's equilibrium resonance and ensure that their working speed does not excite these special resonances of the machine.
When WZ-3C uses eddy current sensors as motor speed measurement sensors, it can monitor the speed of the machine when it is driving (at low speed), which is called zero speed.
The motor may suddenly rotate in reverse during operation, which can cause extremely serious damage to the motor. Therefore, the identification and parking protection of motor reverse rotation are also essential in monitoring. Therefore, it is necessary to use some motor speed measurement sensors to monitor the actual operation of the motor, take preventive measures in advance, and avoid unnecessary losses!
1、 Introduction:
The WZ-3C intelligent transient tachometer adopts an ARM based intelligent speed monitoring and protection instrument, coupled with LH510 magnetic resistance speed sensor and LH520 gear speed sensor, which can measure the speed and linear velocity of various rotating machinery axles, gears, and racks. Suitable for the system design and use of TSI rotating mechanical devices, it can be widely applied in industries such as power, machinery, chemical, metallurgy, etc. Provide multiple parameter measurements and early fault prediction for the safe operation of rotating machinery.
2、 Main functions:
Monitoring and protection of the rotational speed of rotating machinery such as steam turbines, coal mills, fans, reducers, water pumps, centrifuges, balancing machines, and air compressors.
3、 Function Description:
1. The measured value and alarm set value can be displayed separately on the LED digital tube.
2. When the alarm setting value is exceeded, the alarm indicator light will turn on, and at the same time, a switch signal will be output on the rear panel to protect the monitored equipment. The alarm setting delay can be adjusted within the range of 1-60 seconds to prevent false alarms caused by on-site interference..
3. Equipped with a current output interface, it can be connected to devices such as computers, DCS, PLC systems, and paperless recorders.
4. It has power up and power down detection functions, sensor disconnection detection functions, and cuts off alarm and shutdown output circuits, effectively suppressing instrument false alarms.
4、 Electrical indicators:
1. Input signal: Can accept LH510 reluctance speed sensor signal or gear speed sensor signal
2. Waveform: sine wave or pulse
3. Range: 1-99999rpm
4. Display
(1) Display mode: Five digit 0.8-inch LED digital display
(2) Display accuracy: 1rpm
5. Number of teeth: 1-255 arbitrary
6. Current output: 4-20mA active, output load ≤ 500 Ω
7. Alarm point setting: 0-1 full range
8. Alarm relay: Node capacity 7A/250VAC, normally open contacts, sealing: epoxy resin
9. Working power supply: AC220V ± 10% 50Hz ± 5%
5、 Physical indicators:
1. Overall dimensions:
2. Disk mounted table: 160 (width) x 80 (height) x 160 (depth) mm
3. Hole size: 152 (width) x 76 (height) mm
4. Wall mounted surface: width 190 x height 290 x thickness 92 (mm);
5. Installation size: Bottom 170 x Height 272 (mm)
6、 Environmental indicators:
1. Temperature: -10 ℃ to+60 ℃, relative humidity ≤ 95%
2. Usage environment: There is no corrosiveness or strong magnetic field in the surrounding area
7、 Ordering Guide:
1. Disk loading table: WZ-3C-AXX-BXX-CXX
2. Range selection AXX:
(1)01-0~3500rpm
(2)02-0~4000rpm
(3)03-0~5000rpm
(4) 04- Other ranges
3. Current output BXX:
(1)01-4~20mA
(2)02-0~10mA
4. Number of teeth CXX:
(1) 01-1 tooth
(2) 02-60 teeth
(3) 03- Other number of teeth