Operating Standard FMU30-AAHEAAGGF German E+H Ultrasonic Level Gauge
The sensor directly emits ultrasonic pulse signals to the surface of the medium.
The pulse signal is reflected on the surface of the medium, and the reflected signal is received by the sensor.
The instrument measures the time difference between transmitting and receiving pulse signals.
Calculate the distance between the sensor diaphragm and the surface of the medium based on time difference and sound velocity.
[AA] Certification: Non explosion proof occasions
[H] Display, operation: on-site envelope display, buttons
[E] Electrical connection: Cable sealing sleeve M20, IP68
[AA] Sensor; Range; Blind spot: 1-1/2 '; 5m liquid/2m solid; 0.25m
[GGF] Process connection: Thread ISO228 G1-1/2, PP
Power/Communicationtwo-wire system
FMU30 ultrasonic level gauge liquid range: 5m OR 8m
Resolution: 1mm
精度: ±3 mm OR 0.2%
Blind spot: 25cm or 35cm
Power supply: 24VDC (standard); 220VAC (optional)
FMU30 ultrasonic level gauge display: clear multi line text graphic display, envelope line display
Output: 4-20mA
Process connection: 1-1/2 "(5m), 2" (8m)
Shell material: F16 plastic transparent display cover
Advantages and Characteristics of FMU30 Ultrasonic Level Gauge
It is an ideal upgrade substitute for FMU230 and FMU231
Good protection level and high cost-effectiveness
Menu guidance function, easy to achieve on-site operation
measurement accuracy+/-3 mm or+/-0.2% of the set range
ambient temperature-20 °C. ..+60 °C (-4 °F...+140 °F)
process temperature-20 °C. ..+60 °C (-4 °F...+140 °F)
Process pressure (absolute pressure)/overpressure limit value0.7 bar . .. 3 bar abs (10 psi ... 44 psi)
Main liquid receiving componentsPP/EPDM
process connectionG 1-1/2'
G 2'
Blind spot distance1 1/2 'sensor: 0.25m
2 'sensor: 0.35m
measure distance1-1/2 'sensor: 2 m (6.6 ft)
2 'Sensor: 3.5 m (11 ft)
output4...20 mA
Application restrictionsPay attention to the measurement range diagram