Overview
The GSS800B-IR3/UV point type infrared flame detector consists of three infrared sensors and an optical filter. The main sensor has high sensitivity to open flames generated by the combustion of hydrocarbons, while the other three infrared sensors detect background light source interference from ambient light and thermal radiation. The detector has multiple signal processing algorithms, combined with logical comprehensive judgment of flame flicker frequency, upward false alarm suppression, and fire detection performance
Product Details

GSS800B-IR3/UV point type infraredflame detectorIt contains three infrared sensors and an optical filter. The main sensor has high sensitivity to open flames generated by the combustion of hydrocarbons, while the other three infrared sensors detect background light interference from ambient light and thermal radiation. The detector has multiple signal processing algorithms, combined with logical comprehensive judgment of flame flicker frequency, to suppress false alarms and fire detection performance. The special fire signal processing method and multi-sensor detection technology greatly improve the sensitivity and response time of the detector. The sensitivity of the detector can be automatically adjusted according to changes in the usage environment,flame detectorSuitable for liquid and gas fires, open flames accompanied by smoke, and places where explosions occur

Spectral range of response

4.4μm、5.0μm、3.8μm、185-260nm

response time

6s

field of view

120°

Flame sensitivity

Level I

ambient temperature

-10~55℃

ambient humidity

≤95%RH

pressure range

86~106Kpa

Working Voltage

DC24V

operating current

Monitoring current ≤ 25mA, alarm current ≤ 50mA

execution standard

GB15631-2008、GB12791-2006

Explosion-proof rating

EX d ⅡC T6 Gb

Protection level

IP66

signal output

Passive switch quantity RS485

Installation method

Wall mounted or suspended

Cable outlet thread

20mmX1.5mm Free Conversion G1/2 Optional

Overall dimensions

(190X160X110)mm

Shell material

die-cast aluminum

weight

1Kg

advantage

Dustproof, explosion-proof, and corrosion-resistant

alarm method On site sound and light alarm
wiring method Dual cavity structure, rear plug-in terminal block